At Marinetech Safety and Shipping Corporation, we provide a comprehensive range of fixed fire fighting equipment to ensure your vessel's safety. Our solutions are designed to meet international safety standards, offering reliable and effective fire suppression capabilities.
| Operation voltage | DC18V~26V |
| Consumption: Monitoring current Alarm current | ≤350uA ≤1.5mA |
| Technical standard | EN54-7 |
| Indicator | Red, flash in normal, light steady in alarm. |
| Operation temperature | -25℃~70℃ |
| Relative humidity | ≤95% |
| Dimension | Φ90×41.5 mm3 |
| Weight | 100g |
| Color | Ivory-white |
| IP degree | IP44 (Include water-proof detector base ) |
| Material | ABS |
| Operation voltage | 14-22V DC |
| Quiescent current | 300 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Alarm current | 1.3mA |
| Temperature range | -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4) |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-7:2000 |
| Classification: | Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga |
| Operation voltage | 14 22V DC |
| Quiescent current | 340 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Alarm current | 1.3mA |
| Temperature range | -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4) |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-7:2000 |
| Classification: | Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga |
| Operation voltage | 17-28V DC |
| Quiescent current | 300 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Power-up surge current | 1mA |
| Alarm current | 3.5mA |
| Temperature range | -30°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-7:2000 |
| IP Degree: | IP 44 |
| Dimensions: | 100mm diameter X 50mm (height in base) |
| Weight: | 160g (detector in base) |
| Operation voltage | 17-28V DC |
| Quiescent current | 300 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Power-up surge current | 1mA |
| Alarm current | 3.5mA |
| Temperature range | -40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-7:2000 |
| IP Degree: | IP 44 |
| Dimensions: | 100mm diameter X 50mm (height in base) |
| Weight: | 160g (detector in base) |
| Operation voltage | 17-28V DC |
| Quiescent current | 400 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Power-up surge current | 1mA |
| Alarm current | 3.5mA |
| Temperature range | -40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-7:2001 |
| IP Degree: | IP 54 |
| Dimensions: | 100mm diameter X 50mm (height in base) |
| Weight: | 160g (detector in base) |
| Operation voltage | DC18V~30V |
|
Consumption: Monitoring current Alarm current |
DC24V: ≤25mA DC24V: ≤35mA |
| Technical standard | EN54-10 |
| Indicator | The period of power on, green steady. Normal:green flashing. Alarm: red steady. |
| Sensitivity | CLASS:1 |
| Field of view | ≤90º |
| Operation temperature | -25℃~70℃ |
| Relative humidity | ≤95% |
| Dimension | 124×118×122 mm3 |
| Weight | 1.9Kg |
| Color | Silver |
| IP degree | IP66 |
| Material | Aluminum |
| Operation voltage | 17-28V DC |
| Quiescent current | 2.8mA |
| Power-up surge current | 9mA |
| Alarm current | 4.2mA |
| Spectral response | 0.75~2.7um |
| Sensitivity | Class 1 or 3, EN54-10 |
| Field of view | 90 cone |
| Temperature range | 40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54 10 |
| IP Degree: | IP 66 |
| Operation voltage | DC18V~26V |
|
Consumption: Monitoring current Alarm current |
≤350uA ≤1.5mA |
| Technical standard | EN54-5 |
| Indicator | Red, flash in normal, light steady in alarm |
| Sensitivity | Category:A2 |
| Operation temperature | -25℃~70℃ |
| Relative humidity | ≤95% |
| Dimension | Φ90×41.5 mm3 |
| Weight | 100g |
| Color | Ivory-white |
| IP degree | IP44 (Include water-proof detector base ) |
| Material | ABS |
| Operation voltage | 14-22V DC |
| Quiescent current | 300 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Alarm current | 1.3mA |
| Temperature range | -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4) |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-5:2000 |
| Classification: | Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga |
| Operation voltage | 17-28V DC |
| Quiescent current | 400 μ Α |
| Supply wiring | Two-wire supply, polarity sensitive |
| Power-up surge current | 1mA |
| Alarm current | 3.5mA |
| Temperature range | -40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54-5:2001 |
| IP Degree: | IP 54 |
| Dimensions: | 100mm diameter X 50mm (height in base) |
| Weight: | 160g (detector in base) |
| Operation voltage | DC18V~26V |
|
Consumption: Monitoring current Alarm current |
≤2.0mA ≤2.8mA |
| Technical standard | EN54-10 |
| Indicator | Red, flash in normal, light steady in alarm. |
| Sensitivity | Class:3 |
| Field of view | ≤90º |
| Operation temperature | -25℃~70℃ |
| Relative humidity | ≤95% |
| Dimension | Φ104×31 mm3 |
| Weight | 100Kg |
| Color | Ivory-white |
| IP degree | IP44 Include water-proof detector base) |
| Material | ABS |
| Operation voltage | DC18V~26V |
|
Consumption: Monitoring current Alarm current |
Loop:≤600uA;DC24V: ≤12mA Loop:≤3.5mA;DC24V: ≤22mA |
| Technical standard | EN54-10 |
| Indicator | Red, flash in normal, light steady in alarm. |
| Sensitivity | Class:2 |
| Field of view | ≤90º |
| Operation temperature | -25℃~70℃ |
| Relative humidity | ≤95% |
| Dimension | 124x118x122 mm3 |
| Weight | 1.9Kg |
| Color | Silver |
| IP degree | IP66 |
| Material | Aluminum |
| Operation voltage | 17-28V DC |
| Quiescent current | 2.8mA |
| Power-up surge current | 9mA |
| Alarm current | 4.2mA |
| Spectral response | 185~260nm |
| Sensitivity | Class 1 or 3, EN54-10 |
| Field of view | 90 cone |
| Temperature range | 40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54 10 |
| IP Degree: | IP 66 |
| Operation voltage | 17-28V DC |
| Quiescent current | 2.8mA |
| Power-up surge current | 9mA |
| Alarm current | 4.2mA |
| Spectral response | 185~260nm, 0.75~2.7um |
| Sensitivity | Class 1 or 3, EN54-10 |
| Field of view | 90 cone |
| Temperature range | 40°C ~ +70°C |
| Humidity (no condensation or icing) | 0 ~ 95%RH |
| Environment: | EN54 10 |
| IP Degree: | IP 66 |
| Main power* | AC 110/220V (+10%~-15%);50HZ/60HZ |
| Emergency power* | AC 110/220V (+10%~-15%);50HZ/60HZ |
| Ship's DC power | DC 24V±10% |
| Battery inside | DC 24V,4AH |
| Power consumption | In monitoring state: ≤ 10W; In alarm state: ≤ 12W |
| Loop board number | 2 |
| Each loop board capacity | 4 ring loops, max. 128 detectors or manual call points in each loop |
| Time to alarm from manual call point | ≤5 S |
| Time to alarm from detector | ≤10 S |
| Loop Signal transmission distance | ≤1500M |
| Rating distance | ≤1500M(between fire alarm controller and fire alarm repeater) |
| Wiring mode | 1.BS10 series points- 2 wires,non-polarity 2.BS10 series module-4 wires |
| Wire used in the system | Signal line used section is no more than 1.3mm2 or 16AWG screen preventing burning twisted-pair, Power supply line is no more than 2.5me or 12AWG preventing burning twisted-pair |
| Cable | Signal wires is shield twisted wires larger than 1.3mm2 or 16AWG.Power wires is shield twisted wires larger than 1.3mm2 or 16AWG |
| Fire protection zone | Max. 10 zones |
| Output control contact | Fire output (FIRE1-FIRE6) Fire delay output(B1/132), PA output Door hold output Fault output(FAULT1-FAULT4) Power fault output(POW.FAU1/POW.FAU2) System fault output(SYS.FAUVSYS.FAU2) |
| Input contact | IN1/1N2 |
| Operating temperature | 5°C ~ 55°C |
| Relative humidity | ≤ 95% |
| The dimension of main control and display unit | 515 x 525 x 146 (height x width x thickness) mm3 |
| Installation mode | wall type / flush mounting type |
| weight | About 22Kg |
| Fire alarm record | Max 999 instances |
| Other records (include power on, fault alarm, associating, and so on) | Max 999 instances |
| IP degree | IP44 |
| Main power | AC 220V (+10%~-15%),50Hz |
| Emergency power | DC 24V(+30%~-25%) |
| Power | Monitor state:≤3W, Alarm state:≤10W |
| Technical standard | EN54-2,-4 |
| Basic monitor capacity | 2 250,2 loops,250pcs each loop |
| Check period | ≤10s |
| Signal transmitting distance | 1000m(RVS-2×1.0mm2);≤1500m(RVS-2×1.5mm2) |
| Wiring mode | Two bus |
| Voltage between alarm bus | 24V (18V~26V) |
| Operation temperature | 5℃~55℃ |
| Relative humidity | ≤95% |
| Dimensions | 480×380×99 mm3 Wall type, 326×256×124 mm3 Flush mounting type. |
| IP degree | IP32 |
| Main power | AC 220V (+10%~-15%),50Hz |
| Emergency power | AC 220V (+10%~-15%),50Hz |
| Ship’s DC power supply | DC 24V(+10%~-10%) |
| Power | Monitor state:≤2.4W, Alarm state:≤10W |
| Technical standard | EN54-2,-4 |
| Signal transmit distance | 1000m(RVS-2×1.0mm2);≤1500m(RVS-2×1.5mm2) |
| Using cable | Signal wire is 1.5mm2 marine communication cable. Power supply wire is 25mm2 power cable. |
| Main power | AC 220V (+10%~-15%),50Hz |
| Ship’s DC power supply | DC 24V(+10%~-10%) |
| Power | Monitor state: ≤2.4W, Alarm state:≤10W |
| Fire extinguishing basic control capacity | 8 fire extinguishing zones, each of zone start current is no more than 1A, meanwhile, start each of zone total current is no more than 3A |
| Each of water pump input | All of them are without fountain often opening touch point |
| Using cable | Signal wire is 1.5mm2 marine communication cable Power supply wire is 25mm2 power cable. |
| Operation temperature | 5℃~55℃ |
| Relative humidity | ≤95% |
| Dimension | 290 × 180 × 51 mm3 (Flushing mounting fire alarm control panel) 540×380×140 mm3 (Interface box) |
| IP degree | IP32 |