Fixed Fire Fighting Equipment

Home / Supplies

Fixed Fire Fighting Equipment

At Marinetech Safety and Shipping Corporation, we provide a comprehensive range of fixed fire fighting equipment to ensure your vessel's safety. Our solutions are designed to meet international safety standards, offering reliable and effective fire suppression capabilities.

Smoke Detectors

Operation voltage DC18V~26V
Consumption: Monitoring current Alarm current ≤350uA ≤1.5mA
Technical standard EN54-7
Indicator Red, flash in normal, light steady in alarm.
Operation temperature -25℃~70℃
Relative humidity ≤95%
Dimension Φ90×41.5 mm3
Weight 100g
Color Ivory-white
IP degree IP44 (Include water-proof detector base )
Material ABS
Operation voltage 14-22V DC
Quiescent current 300 μ Α
Supply wiring Two-wire supply, polarity sensitive
Alarm current 1.3mA
Temperature range -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4)
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-7:2000
Classification: Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga
Operation voltage 14 22V DC
Quiescent current 340 μ Α
Supply wiring Two-wire supply, polarity sensitive
Alarm current 1.3mA
Temperature range -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4)
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-7:2000
Classification: Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga
Operation voltage 17-28V DC
Quiescent current 300 μ Α
Supply wiring Two-wire supply, polarity sensitive
Power-up surge current 1mA
Alarm current 3.5mA
Temperature range -30°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-7:2000
IP Degree: IP 44
Dimensions: 100mm diameter X 50mm (height in base)
Weight: 160g (detector in base)
Operation voltage 17-28V DC
Quiescent current 300 μ Α
Supply wiring Two-wire supply, polarity sensitive
Power-up surge current 1mA
Alarm current 3.5mA
Temperature range -40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-7:2000
IP Degree: IP 44
Dimensions: 100mm diameter X 50mm (height in base)
Weight: 160g (detector in base)
Operation voltage 17-28V DC
Quiescent current 400 μ Α
Supply wiring Two-wire supply, polarity sensitive
Power-up surge current 1mA
Alarm current 3.5mA
Temperature range -40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-7:2001
IP Degree: IP 54
Dimensions: 100mm diameter X 50mm (height in base)
Weight: 160g (detector in base)

IR Flame Detectors

Operation voltage DC18V~30V
Consumption:
Monitoring current
Alarm current
DC24V: ≤25mA
DC24V: ≤35mA
Technical standard EN54-10
Indicator The period of power on, green steady. Normal:green flashing. Alarm: red steady.
Sensitivity CLASS:1
Field of view ≤90º
Operation temperature -25℃~70℃
Relative humidity ≤95%
Dimension 124×118×122 mm3
Weight 1.9Kg
Color Silver
IP degree IP66
Material Aluminum
Operation voltage 17-28V DC
Quiescent current 2.8mA
Power-up surge current 9mA
Alarm current 4.2mA
Spectral response 0.75~2.7um
Sensitivity Class 1 or 3, EN54-10
Field of view 90 cone
Temperature range 40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54 10
IP Degree: IP 66

Heat Detectors

Operation voltage DC18V~26V
Consumption:
Monitoring current
Alarm current
≤350uA
≤1.5mA
Technical standard EN54-5
Indicator Red, flash in normal, light steady in alarm
Sensitivity Category:A2
Operation temperature -25℃~70℃
Relative humidity ≤95%
Dimension Φ90×41.5 mm3
Weight 100g
Color Ivory-white
IP degree IP44 (Include water-proof detector base )
Material ABS
Operation voltage 14-22V DC
Quiescent current 300 μ Α
Supply wiring Two-wire supply, polarity sensitive
Alarm current 1.3mA
Temperature range -20°C ~ +60°C, -20°C ~ +45°C (T5), -20°C ~ +60°C (T4)
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-5:2000
Classification: Ex ia IIC T5 -20°C ≤Ta 45°C (T4 ≤60°C)Ga
Operation voltage 17-28V DC
Quiescent current 400 μ Α
Supply wiring Two-wire supply, polarity sensitive
Power-up surge current 1mA
Alarm current 3.5mA
Temperature range -40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54-5:2001
IP Degree: IP 54
Dimensions: 100mm diameter X 50mm (height in base)
Weight: 160g (detector in base)

UV Flame Detectors

Operation voltage DC18V~26V
Consumption:
Monitoring current
Alarm current
≤2.0mA
≤2.8mA
Technical standard EN54-10
Indicator Red, flash in normal, light steady in alarm.
Sensitivity Class:3
Field of view ≤90º
Operation temperature -25℃~70℃
Relative humidity ≤95%
Dimension Φ104×31 mm3
Weight 100Kg
Color Ivory-white
IP degree IP44 Include water-proof detector base)
Material ABS
Operation voltage DC18V~26V
Consumption:
Monitoring current
Alarm current
Loop:≤600uA;DC24V: ≤12mA
Loop:≤3.5mA;DC24V: ≤22mA
Technical standard EN54-10
Indicator Red, flash in normal, light steady in alarm.
Sensitivity Class:2
Field of view ≤90º
Operation temperature -25℃~70℃
Relative humidity ≤95%
Dimension 124x118x122 mm3
Weight 1.9Kg
Color Silver
IP degree IP66
Material Aluminum
Operation voltage 17-28V DC
Quiescent current 2.8mA
Power-up surge current 9mA
Alarm current 4.2mA
Spectral response 185~260nm
Sensitivity Class 1 or 3, EN54-10
Field of view 90 cone
Temperature range 40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54 10
IP Degree: IP 66
Operation voltage 17-28V DC
Quiescent current 2.8mA
Power-up surge current 9mA
Alarm current 4.2mA
Spectral response 185~260nm, 0.75~2.7um
Sensitivity Class 1 or 3, EN54-10
Field of view 90 cone
Temperature range 40°C ~ +70°C
Humidity (no condensation or icing) 0 ~ 95%RH
Environment: EN54 10
IP Degree: IP 66

Fire Alarm System Control Panels

Main power* AC 110/220V (+10%~-15%);50HZ/60HZ
Emergency power* AC 110/220V (+10%~-15%);50HZ/60HZ
Ship's DC power DC 24V±10%
Battery inside DC 24V,4AH
Power consumption In monitoring state: ≤ 10W; In alarm state: ≤ 12W
Loop board number 2
Each loop board capacity 4 ring loops, max. 128 detectors or manual call points in each loop
Time to alarm from manual call point ≤5 S
Time to alarm from detector ≤10 S
Loop Signal transmission distance ≤1500M
Rating distance ≤1500M(between fire alarm controller and fire alarm repeater)
Wiring mode 1.BS10 series points- 2 wires,non-polarity 2.BS10 series module-4 wires
Wire used in the system Signal line used section is no more than 1.3mm2 or 16AWG screen preventing burning twisted-pair, Power supply line is no more than 2.5me or 12AWG preventing burning twisted-pair
Cable Signal wires is shield twisted wires larger than 1.3mm2 or 16AWG.Power wires is shield twisted wires larger than 1.3mm2 or 16AWG
Fire protection zone Max. 10 zones
Output control contact Fire output (FIRE1-FIRE6) Fire delay output(B1/132), PA output Door hold output Fault output(FAULT1-FAULT4) Power fault output(POW.FAU1/POW.FAU2) System fault output(SYS.FAUVSYS.FAU2)
Input contact IN1/1N2
Operating temperature 5°C ~ 55°C
Relative humidity ≤ 95%
The dimension of main control and display unit 515 x 525 x 146 (height x width x thickness) mm3
Installation mode wall type / flush mounting type
weight About 22Kg
Fire alarm record Max 999 instances
Other records (include power on, fault alarm, associating, and so on) Max 999 instances
IP degree IP44
Main power AC 220V (+10%~-15%),50Hz
Emergency power DC 24V(+30%~-25%)
Power Monitor state:≤3W, Alarm state:≤10W
Technical standard EN54-2,-4
Basic monitor capacity 2 250,2 loops,250pcs each loop
Check period ≤10s
Signal transmitting distance 1000m(RVS-2×1.0mm2);≤1500m(RVS-2×1.5mm2)
Wiring mode Two bus
Voltage between alarm bus 24V (18V~26V)
Operation temperature 5℃~55℃
Relative humidity ≤95%
Dimensions 480×380×99 mm3 Wall type, 326×256×124 mm3 Flush mounting type.
IP degree IP32
Main power AC 220V (+10%~-15%),50Hz
Emergency power AC 220V (+10%~-15%),50Hz
Ship’s DC power supply DC 24V(+10%~-10%)
Power Monitor state:≤2.4W, Alarm state:≤10W
Technical standard EN54-2,-4
Signal transmit distance 1000m(RVS-2×1.0mm2);≤1500m(RVS-2×1.5mm2)
Using cable Signal wire is 1.5mm2 marine communication cable. Power supply wire is 25mm2 power cable.
Main power AC 220V (+10%~-15%),50Hz
Ship’s DC power supply DC 24V(+10%~-10%)
Power Monitor state: ≤2.4W, Alarm state:≤10W
Fire extinguishing basic control capacity 8 fire extinguishing zones, each of zone start current is no more than 1A, meanwhile, start each of zone total current is no more than 3A
Each of water pump input All of them are without fountain often opening touch point
Using cable Signal wire is 1.5mm2 marine communication cable Power supply wire is 25mm2 power cable.
Operation temperature 5℃~55℃
Relative humidity ≤95%
Dimension 290 × 180 × 51 mm3 (Flushing mounting fire alarm control panel) 540×380×140 mm3 (Interface box)
IP degree IP32